UL 2808 Certified Split-Core Current Transformer

Split-Core Current Transformer

Application:

Maximize your AC power system’s efficiency with the CTSR family of mini split-core current transformers. Designed for seamless integration into space-constrained environments, these transformers offer a swift and straightforward installation process.

Experience unparalleled accuracy in AC current measurement, thanks to the high-performance magnetic core housed within a compact form factor. Durability meets convenience with the robust design, featuring a mechanical hinge that ensures repeated, reliable open/close operations. The precise alignment and firm closure of the core halves post-installation guarantee the transformer’s long-term consistency and measurement precision.

Choose the UL 2808 certified CTSR split-core current transformers for a dependable solution that promises consistent and precise AC current monitoring, vital for the optimal performance of your electric power distribution system.

Features:

  • Characterized by high sensitivity, accuracy, linearity, and minimum phase shift for highly accurate AC current measurement.
  • Product warranty of 36 months.
  • ModelRated Primary Current
    Maximum Continuous (Ampere)
    Secondary @ Rated Primary CurrentOpening
    CTSR0105A to 100A
    • mV: Standard 0.333V @ Rated Primary Current
    • Optional: Any voltage between 0.100V and 3.530V
    • mA Standard winding ratios:
    • 1:1000, 1:2000, 1:2500, 1:3000
    • Maximum 100mA
    11.0mm (0.40″)
    CTSR02450A to 300A
    • mV: Standard 0.333V @ Rated Primary Current
    • Optional: Any voltage between 0.100V and 3.530V
    • mA Standard winding ratios:
    • 1:1000, 1:2000, 1:2500, 1:3000
    • Maximum 300mA
    24.0mm (0.94″)
    CTSR36200A to 600A
    • mV: Standard 0.333V @ Rated Primary Current
    • Optional: Any voltage between 0.100V and 3.530V
    • mA Standard winding ratios:
    • 1:1000, 1:2000, 1:2500, 1:3000
    • Maximum 500mA
    36.0mm (1.42″)

Performance:

  • Accuracy Class: 0.5, 1.0 (IEC 61869-2)
  • Accuracy: < 1% error
  • Phase Angle: < 120 minutes
  • Linearity: ±1% from 5% to 130% of rated primary current

Specifications:

  • Input Frequency: 50 to 400 HZ
  • Maximum Primary Voltage: 720 VAC
  • Dielectric Withstand Voltage: 4,000V for 10 seconds
  • Dielectric Resistance: 100 MOhms @ 500 VDC
  • Operating temperature: -20ºC to +55ºC
  • Construction:
    • Ferrite core material or Silicon Steel CRGO core material
    • Epoxy encapsulated
    • Case: UL flame retardant rating 94V-0
  • Standard Wire Lead: 0.61m (2 ft.), AWM/ UL 1015, twisted pair … configurable to desired lead length./li>
  • UL 2808 Listed Certification (E468983)
  • RoHS Compliant

Standard Size Mini Split-Core Current Transformer:Mini Split-Core Current Transformer

  • CTSR010 standard models – 11.0mm (0.40in) window
  • CTSR024 standard models – 24.0mm (0.94in) window
  • CTSR036 standard models – 36.0mm (1.42in) window
 



Many of our products can be designed and manufactured to meet the specific application requirements. For a no obligation technical evaluation, contact us with your specific performance requirements.